HOT WATER MODELS V-33 THROUGH V-180INSTALLATION AND OPERATING INSTRUCTIONSGAS-FIRED CAST-IRON BOILERS FOR NATURAL AND L.P. PROPANE GASESCONTENTS . .
10VICTORYFigure 9. Vertical Venting (3 IN.): All Victory ModelsAll items shown below are REQUIRED. All vent joints must be LIQUID and PRESSURE TIGHT.
VICTORY 11at test pressures equal to or less than 1/2 PSIG.D. All gas piping used should be inspected thoroughly forcleanliness before makeup. A sedim
12VICTORYB. PUMP LOCATION-Locating low-head pump(s) onreturn to boiler is acceptable for smaller boiler sizes inresidences of one or two stories. The
VICTORY 138. Turn on all electric power to the appliance.9. Set thermostat to desired setting.10. If the appliance will not operate, follow the instru
14VICTORY2. Safety Shutdown Checkouta. For proper operation the pilot should engulf thethermocouple, powerpile generator or flame sen-sor as shown bel
VICTORY 15burners as described on page 13.*To clean burners run a clean flue brush up the tubeuntil all foreign matter is removed.IV. SAFETY CHECK FOR
16VICTORYAPPENDIX ARemoval Of Existing Boiler From Common Vent System"At the time of removal of an existing boiler, the followingsteps shall be f
VICTORY 17Sequence of Operations Wiring DiagramsCAUTION: Label all wires prior to disconnection when servicing controls.Wiring errors can cause improp
18VICTORYPUMP OR VALVE ZONING OF WATER BOILERSCOMBINATION CONTROLS WITH T TV Z TERMINALS*Pump Zoning system using R845 Relay.One R-845A nee
VICTORY 19BURNERS FAIL TO OPERATECAUSE1. Safety pilot out, or flame too low.2. Gas supply valve shut off.3. Electric switch open.4. Blown or defective
2 VICTORYDimensions (inches)Figure 1. Left End ViewFigure 2. Front ViewFigure 3. Right End ViewNOTE: Height Dimension increases to 30-3/16" and d
20 VICTORYPIPING A HEATING - COOLING SYSTEM TO A WATERBOILER AND CHILLERFigure below illustrates a method of piping a heating-coolingsystem to a wate
VICTORY 3INSTALLATION REQUIREMENTSThe installation must conform to the requirements of theauthority having jurisdiction or, in the absence of suchrequ
4 VICTORYReference Table No. *ApplianceConnector Requirements*(ANSI Z223.1)Victory Boilers Type “B” See table 11-1 for minimum and maximum of vent 11-
VICTORY 5HORIZONTAL PRESSURE VENTINGAll VICTORY models are certified for horizontal pressureventing with the following restrictions:1. Vent MaterialA.
Model/Vent SizeV-90, V-120, V-150 and V-180 boilers may be vented into achimney (see “Chimney and type “B” venting” paragraph onpage 4) or into a type
VICTORY 7Figure 6b. Venting with “B” vent or metal-lined chimney for V-90, V-120, V-150 and V-180 onlyMinimum vent connectors diameter is 5 inches. It
8 VICTORYFigure 7. Horizontal Venting (3 IN.): All Victory ModelsAll items shown below are REQUIRED. All vent joints must be LIQUID and PRESSURE TIGHT
VICTORY9Figure 8. Horizontal Venting (3 IN.): All Victory ModelsAll items shown below are REQUIRED. All vent joints must be LIQUID and PRESSURE TIGHT