XXLL--22000000
OIL-FIRED WATER BOILERS/NO. 2 OIL
INSTALLATION AND OPERATING INSTRUCTIONS
SAFETY WARNING:
KEEP BOILER AREA CLEAR AND FREE FROM COM-
BUSTIBLE MATERIALS, GASOLINE AND OTHER FLAM-
MABLE VAPORS AND LIQUIDS. FAILURE TO ADHERE TO
ABOVE SAFETY WARNING, MAY RESULT IN PERSONAL
INJURY OR DEATH AND PROPERTY DAMAGE.
CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE
Ratings and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Installation Requirements:
Boiler Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Chimney Requirements . . . . . . . . . . . . . . . . . . . . . . . . . .3
Air Supply and Venting . . . . . . . . . . . . . . . . . . . . . . . . . .3,4
Controls and Accessories . . . . . . . . . . . . . . . . . . . . . . . . .5
Piping for Water Units . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Installing Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Oil Supply Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Wiring the Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Vent Piping and Draft Regulator . . . . . . . . . . . . . . . . . . . .5
Operating Instructions:
Precautions Before Starting . . . . . . . . . . . . . . . . . . . . . . .7
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Cleaning and Filling New Water Boiler . . . . . . . . . . . . . . .8
Care and Maintenance:
Extended Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Freezing Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Oil Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
General Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Burner Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11,12
I
I
M
M
P
P
O
O
R
R
T
T
A
A
N
N
T
T
:
:
The installation of this equipment must con-
form to the requirements of the authority having jurisdiction
or, in the absence of such requirements, to the Installation of
Oil Burning Equipment, ANSI/NFPA 31, latest edition, and to
the National Electrical Code ANSI/NFPA 70, latest edition.
The installation must also conform to the additional require-
ments in this Slant/Fin Instruction Manual. Where there is any
difference, the more stringent requirement shall govern.
In addition, where required by the authority having jurisdiction,
the installation must conform to American Society of Mechanical
Engineers Safety Code for Controls and Safety Devices for
Automatically Fired Boilers, No. CSD-1, latest edition.
THIS MANUAL MUST BE LEFT WITH OWNER AND
SHOULD BE HUNG ON OR ADJACENT TO THE BOILER
FOR REFERENCE.
IMPORTANT: This boiler must be installed, serviced and
repaired by a trained, experienced, service technician,
licensed for the installation and servicing of oil burning hot
water heating system equipment or otherwise qualified by the
author
ities having jurisdiction over the installation.
Printed in U.S.A.305 Publication No. XL-40
Part No. 48-0090 Revision C
Vista de pagina 0
1 2 3 4 5 6 ... 14 15

Indice de contenidos

Pagina 1 - XXLL--22000000

XXLL--22000000OIL-FIRED WATER BOILERS/NO. 2 OILINSTALLATION AND OPERATING INSTRUCTIONSSAFETY WARNING:KEEP BOILER AREA CLEAR AND FREE FROM COM-BUSTIBLE

Pagina 2

XL-200010

Pagina 3

BURNER DATA—CARLIN BURNERS FOR PACKAGED BOILERS ONLYXL-200011XL-20 99-FRD 0.65 0.65 70° A DELAVAN 100 0 50 Closed71399-00F-XL-20 0.65 70° W DELAVAN 10

Pagina 4

XL-200012BURNER DATA—BECKETT BURNERS FOR PACKAGED BOILERS ONLYXL-20 (4) AFG F0 0.65 0.65 80° A DELAVAN 100 7 Blank/Closed 33/8SF2201XL-30HAFG F3 0.85

Pagina 5

BURNER DATA - RIELLO BURNERS FOR PACKAGED BOILERS ONLY(RIELLO R-40 SERIES W/SHORT TUBE)† Air shutter and head settings shown are approximate ONLY. See

Pagina 6

XL-200014BURNER DATA - RIELLO (continued)REGULATION OF THE TURBULATOR AND AIR SHUTTERFOR PROPER COMBUSTIONTurbulator Setting1. Loosen nut, 1, then tur

Pagina 7

SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600FAX: (516) 484-5921 • Canada:Slant/Fin LTD/LTEE,Mississauga, Ontariowww.slantfin.c

Pagina 8

XL-20002XL-20 0.65 91,000 78 68 8 x8x15 6 x 15 83.56 811/1649/166¶ 11/4253/8XL-30H 0.85 119,000 104 90 8 x8x15 6 x 15 86.00 123/1665/16611/4287/8X

Pagina 9

THE INSTALLATION INSTRUCTIONS IN THIS MANUALARE ABBREVIATED. SEE THE FRONT COVER OF THISMANUAL FOR REFERENCES TO CODES AND STAN-DARDS.BOILER LOCATIONP

Pagina 10

tion, heavy sooting and health hazards. Any oil-fired boilermust have a steady draft* and an ample supply of combustionair at all times during firing.

Pagina 11

XL-20005Figure 3a.Appliances located in confined spaces. Air frominside the building. See Table 2 (2.3).Figure 3b.Appliances located in confined space

Pagina 12

XL-20006The opening size recommendation just given is for guidanceonly. It is the installer’s responsibility to provide air for combus-tion and ventil

Pagina 13

DOMESTIC HOT WATERFor Indirect-fired storage water heater application, seeSlant/Fin publication WH-10, Sizing Guide WH-SG andInstallation manual WH-40

Pagina 14

smoke and dry soot formation in the fire box.F. If smoke reading is satisfactory, but CO2can not beincreased to a satisfactory level (12%) or overfire

Pagina 15 - Mississauga, Ontar

6. Use the flue brush to clean the pinned fluewaysbetween the sections.† A wire brush may be usedto remove any carbon accumulation that may havedevelo